ERMS Series Modular UPS

19" shelf

Truly Modular UPS

Full UPS functioned UPS Module


6kVA - 36kVA 

6kVA UPS Module


High Frequency MODULAR UPS

Modular,hot-swappable, field-replaceable Monitor, UPS module. 

Embedded modular power protection with ultra high availability and efficiency for Small Date Center.


    Description

    Overview:

    ERMS series UPS is an embedded modular UPS of low and medium power developed by SCU. With flexible structure, it could be embedded in standard 19 inch cabinet or work independently for de-centralized power supply. ERMS provides integrated power solution. Internal battery module and output PDU are available for optional configuration.

    It features superb input and output performance indexes. As a product with the smallest size, the highest efficiency and the greatest power density in the industry, it boasts extremely high cost-efficiency.


    Feature:

    (1)19’’ shelf embedded structure

    (2)UPS module: 6 kVA; System: 12kVA, 24 kVA, 36kVA.

    (3)Great performance index

    overall efficiency ≥ 95%(AC-AC), inverter efficiency ≥ 98%(DC-AC), THDI ≤ 3%, and input PF ≥ 0.99

    (4)N+X module-level redundancy UPS System

    (5)Multi-level decentralized control technology and Master-slave synchronization in sequency control which result in eliminate system failure bottleneck

    (6)Each module automatically even shares the input and output current, all UPS modules share batteries

    (7)Battery management: 

    Battery discharge management, auto-transfer between floating and even charging, temperature compensation

    (8)Monitor Function

    C/S-Oriented Architecture SICON Software which is available to monitor multiple UPS up to 600 sets;

    B/S-Oriented Architecture which is available to check via IE

    (9)Standard configuration

    Manual bypass, RS232, RS485, dry contacts, TCP/IP adapter for local and remote communication, 

    (10)Optional configuration

    Input/output Transformer, Battery Bank, IPDS(Intelligent Power Distribution System)


    Application:

    Small server room, network, bank, security, transportation, broadcast&TV network, HealthCare, Communication, Finance

    Model 


    ERMS-12/6

    System Max. Power:    12KVA                                                           

    Module Model:            ERM-06

    Condiguration:           2 slots

    Dimensions:              480*600*132W*D*H(mm)

    Wire in/out mode: 1/1



    ERMS-24/6

    System Max. Power:    24KVA

    Module Model:            ERM-06

    Condiguration:           4 slots

    Dimensions:              480*600*220 W*D*H(mm)

    Wire in/out mode: 1/1



    ERMS-36/6

    System Max. Power:   36KVA

    Module Model:           ERM-06

    Condiguration:          6 slots

    Dimensions:             480*600*310W*D*H(mm)

    Wire in/out mode: 1/1, 1/3, 3/1, 3/3


    Systemmodel

    ERMS-12/6

    ERMS-24/6

    ERMS-36/6

    Maximumpower

    12KVA

    24KVA

    36KVA

    Powermodulemodel

    ERM-06

    MainsInput

    Input mode

    3-phase+N+E,1-phase+N+E


    Input voltage

    380V/220±20%,400V/230±20%,415V/240±20%

    Input frequency

    50Hz±10%,60Hz±10%

    Power woke-in (Sec.)

    60sec

    THDI (%)

    <3%

    Input PF

    ≥0.99

    BypassInput

    Input voltage

    380V/220±20%,400V/230±20%,415V/240±20%

    Input frequency

    50Hz,60Hz

    Range of Frequency Synchro

    50Hz±4%,60Hz±4%

    DCInput

    Rated Input voltage

    ±240VDC

    Input voltage tolerance

    ±216V~±246VDC

    Batterycharging


    Charging current limited

    yes

    Charging ability

    10hours(2hoursbackup)

    Stability of charging voltage

    1%

    ACoutput

    UPS power factor

    0.9

    Output voltage

    380V/220VAC,400V/230VAC,415V/240VAC

    Output frequency

    ±4%±0.2%(battery supply)

    Output voltage stability

    ±1%

    Output voltage recovering time

    <20ms(load0~100%change)

    Overload ability

    Operate 10mins with 125% load

    Transfer from mains to battery supply

    0ms

    Transfer from by pass to inverter supply

    <1ms

    Peak factor

    3:1

    Waveformdistortion

    ≤1% ( linear load ),  ≤3%( non-linear load )

    Overall efficiency

    ≥95% (AC~AC),  ≥98% (DC~AC)

    Load share precision

    ≤5%

    Operationenvironment

    Ambient temperature



    -25℃~60℃


    Operating temperature



    -5℃~40℃


    Maximum operation altitude

    ≤1500m 

    Relative humidity

    ≤95% non-cadency

    Protection degree

    IP30

    Cooling

    Aircooling

    Applicable safety standards



    EN62040-1-1:2003     IEC60950-1:2001


    Electromagnetic compatibility

    EN62040-2:2006

    Acoustic noise

    ≤55DB

    Others

    Cabinet

    Standard 19 inch cabinet

    Monitormanagement system

    UPSupervisor

    Interface

    RS232,RS485,2 try contact,TCP/ IPadapter

    Display

    LCD/LED

    Weight(kg)

    12

    16

    20